Signal Isolation Card (Signal Isolator)
Model C10209-000
General Description•Standard Features•Specifications•Application Example•Dimensions/Connections
Specifications
A.C. Input
- 115/230 VAC, ±10%, 50/60 Hz, 6.8 VA Max.
Current Input
- 3 selectable ranges with input impedance as shown below. Maximum output is 12 VDC or 24 mADC. Typical output range with max. input is 5 to 10 VDC or 10 to 20 mADC.
Input Range
1 to 5 mADC
4 to 20 mADC
10 to 50 mADC |
Input Impedance
1000 Ohms
270 Ohms
100 Ohms |
Frequency Input
- A sine or square wave input is acceptable with a peak of 1 to 20 V. Input impedance is 100K Ohms. Maximum input frequency is 2000 Hz. GAIN Range (Vout/Fin) = 0.0028 to 0.014. Minimum frequency to give 10 VDC output is approximately 750 Hz. Max. output is limited to 12 VDC or 24 mADC.
Pot. Input
- + 15 VDC, ±5% available to source a 2 to 10 k Ohm external pot. Use 0 to 25 VDC voltage input range.
Summing Input
- This input is not isolated from output. Input: +/- 10VDC max.
|
|
Voltage Input
- 4 selectable ranges with greater than 1 Meg Ohm input impedance. Max. output is approximately 12 VDC or 24 mADC.
Input Range
0 to 25 VDC
0 to 50 VDC
0 to 100 VDC
0 to 200 VDC
|
Gain Range
0.25 to 1.25
0.10 to 0.50
0.05 to 0.25
0.025 to 0.125 |
Trim Range
- (Trim Pot = 10 K Ohms, Bias = 0 VDC) Min. Range: 80 to 100% of output Max. Range: 0 to 100% of output
Isolation Voltage
- 2000 V peak for 1 second, 480 VRMS Max. continuous
Linearity
|
VIEW INSTRUCTION MANUAL
View Brochure
General Description•Standard Features•Specifications•Application Example•Dimensions/Connections
Back to System Interface Components • Back to Product Line
Signal Isolation Card (Signal Isolator)